CBI – DC UPS Adelsystem

All DC-UPSs are protected against reverse polarity, short circuit, overload and the output overvoltage.

Category

Brand

These are switching technology devices with microcontroller, which best optimizes the charging and discharging time of the accumulator, avoiding deep discharge of the batteries. The switching time on the load is zero; switching between the input and the battery is immediate. All DC-UPSs are protected against reverse polarity, short circuit, overload and the output overvoltage.

  • Communication protocols: Modbus RTU, Modbus TCP/IP, SNMP and HTTPS with built-in webserver
  • Internal battery status diagnostics (Lead, AGM, GEL, NiCd, NiMh, Lithium, LiFePO4).
  • Selectable charging curve to maximize system efficiency
  • Durability of the battery over time while enhancing its performance
  • Equipped with relays for power failure and battery fault signaling
  • Compliant with the latest battery management as well as electrical safety standards
  • DIN rail mounting.

Battery start function
  1. No AC grid input
  2. DC-UPS continues to supply backup power from the battery
  3. Interruption of AC power supply longer than expected.
  4. Replacing the battery with a new one
  5. Pressing the START BATTERY button for 3 seconds
  6. DC-UPS restarts ensuring system operation

Key Features

  • Output voltage 12, 24, 48Vdc, even in the absence of power supply
  • Output current 2.5A ÷ 25A, even in the absence of AC mains
  • Fault signaling via relay contact, blink code, and Modbus RTU and TCP/IP protocols
  • Automated power sharing of available power between load and battery charging
  • Output power: 60W, 120W, 240W, 250W, 280W, 500W, 600W
  • Power boost, up to 3 times the rated current available. Ability to handle high current surges
  • DC-UPS and battery self-diagnosis: high voltage; sulfated battery; reverse connection; possible shorted element; short circuit protection
  • “Main or back-up” and “battery failure/discharge” signaling relays with galvanically isolated output contacts
  • Accessories: battery temperature sensor, external display, PC and Modbus connection cables
  • Fast battery recharging for cyclic applications
  • Ultracompact design
  • Temperature operation range -40 ÷ 70°C

Datasheet & Manual

All in one 12Vdc
NAME INPUT OUTPUT DATA SHEET MANUALS TECHNICAL DRAWINGS
CBI123A 110-240-277Vac 3A file-pdf-solid (1) file-pdf-solid (1)
CBI126A 110-240-277Vac 6A file-pdf-solid (1) file-pdf-solid (1)
CBI1210A 110-240-277Vac 10A file-pdf-solid (1) file-pdf-solid (1)
CBI1235A 110-240-277Vac 35A file-pdf-solid (1) file-pdf-solid (1)
All in one 24Vdc
NAME INPUT OUTPUT DATA SHEET MANUALS TECHNICAL DRAWINGS
CBI243A 110-240-277Vac 3A file-pdf-solid (1) file-pdf-solid (1)
CBI245A 110-240-277Vac 5A file-pdf-solid (1) file-pdf-solid (1)
CBI2410A 110-240-277Vac 10A file-pdf-solid (1) file-pdf-solid (1)
CBI2420A 110-240-277Vac 25A file-pdf-solid (1) file-pdf-solid (1)
All in one 48Vdc
NAME INPUT OUTPUT DATA SHEET MANUALS TECHNICAL DRAWINGS
CBI485A 110-240-277Vac 5A file-pdf-solid (1) file-pdf-solid (1)
CBI4810A 110-240-277Vac 12.5A file-pdf-solid (1) file-pdf-solid (1)
All in one 12-24Vdc
NAME INPUT OUTPUT DATA SHEET MANUALS TECHNICAL DRAWINGS
CBI2801224A 110-240-277Vac 280W file-pdf-solid (1) file-pdf-solid (1)
CBI2501224A 100-240-277Vac 140-340 Vdc 250W file-pdf-solid (1) file-pdf-solid (1)
Temperature sensor
NAME INPUT OUTPUT DATA SHEET MANUALS TECHNICAL DRAWINGS
RJTEMP111 RJTEMP113 file-pdf-solid (1)
      RJTEMP451            RJTEMP453               file-pdf-solid (1)
brand

PULS

group

Power Supply